9-6. Brief method for checking the key components
9-6-1. Hydro unit
No.
Component name
Check procedure
1
Water heat exchange
temperature
(TC) sensor
Water inlet temperature
(TWI) sensor
Water outlet temperature
(TWO) sensor
Hot water cylinder temperature
(TTW) sensor
Floor inlet temperature
(TFI) sensor
Remove the connector and measure the resistance value with a tester. (Normal temperature)
Temperature
0 °C
10 °C
20 °C
30 °C
Sensor
Water heat exchange temperature (TC) sensor
33.8
k
Ω
20.35
k
Ω
12.59
k
Ω
7.99
k
Ω
Water inlet temperature (TWI) sensor
Water outlet (TWO) sensor
Hot water cylinder temperature (TTW) sensor
Floor inlet temperature (TFI) sensor