– 19 –
Air to Water Heat Pump
Installation Manual
Wiring between hydro unit and outdoor unit
The dashed lines show on-site wiring.
Connect the system interconnection wires to the identical terminal numbers on the terminal block of each unit.
Incorrect connection may cause a failure.
For the air to water heat pump, connect a power wire with the following specifications.
* Number of wire
×
wire size
Model HWS-
P804HR-E
P1104HR-E
Power supply
220-230 V ~
50 Hz
Maximum running current
22.8 A
Recommended field fuse
25 A
Power supply wire*
3
×
2.5 mm
2
or more
(H07 RN-F or 60245 IEC 66)
Hydro / outdoor connecting wires*
4
×
1.5 mm
2
or more
(H07 RN-F or 60245 IEC 66)
L
N
1
3
2
1
3
2
HWS-P804HR-E
HWS-P1104HR-E
Outdoor unit
Hydro unit
Leakage breaker
Input power
220-230 V ~, 50 Hz
19-EN