– 41 –
Hydro Unit
Installation Manual
Language
• Select a language for the screen text.
(1) Press the [
] / [
] button to select
“Language” on the Initial setting screen, then press
the [
] button.
(2) Press the [
] / [
] button to select
the language, then press the [
] button.
• The factory default is “English”.
FIELD SETTING MENU
(1) Press the [
] button and the [
] button at
same time for 4 seconds or longer on the top screen
to display the “FIELD SETTING MENU” to select
“setting”
Test mode
• Even if the outside air temperature or water
temperature is outside the setting value range,
Heating, Cooling and Hot water supply operation
become possible.
• Since the protection setting is disabled in the TEST
mode, do not continue a test run longer than
10 minutes.
(1) Press the [
] / [
] button to select “Test
mode” on the FIELD SETTING MENU screen, then
press the [
] button.
(2) Press the [
] button to select ON, then press
the [
] button. The
mark appears on the top
screen.
Language
Initial setting(2/2)
Language
SET
Language(1/2)
English
Turkish
French
German
Spanish
FIX
Türkçe
Français
Deutsch
Español
Language(2/2)
Italian
FIX
Italiano
Test mode
FIELD SETTING MENU(1/2)
Floor drying
Forced defrosting
Information input
SET
Alarm history
Test mode
FIELD SETTING MENU(1/2)
Floor drying
Forced defrosting
Information input
SET
Alarm history
Test mode
ON
OFF
FIX
41-EN