Hydro Unit
Installation Manual
EN
Settings by Purpose
Settings when hot water supply function is
not used
• When the hot water supply function is not used, set
DIP SW12-1 on the Hydro Unit board to ON. (Refer
to page 30.)
Setting for cooling
• For Hydro Units that do not perform cooling (those
for floor heating, etc.), procure a motorized 2-way
valve (for cooling) (refer to “Control parts
specifications” on page 21 for the details.) locally and
attach it to the water pipe that is not used for cooling.
Connect the valve cables to terminals TB05 (3) and
(4) of the Hydro Unit.
• Press long the TEST
+ SET
+ SELECT
switches on the remote controller to
change the Hydro Unit function code, and change
address 02 to 0, and then press the SET
button
to enable the function. Press the TEST
button to
exit the setting mode.
• Stick the optional insulator for cooling to the bottom
of the Hydro Unit.
Settings for hot water supply
• Prepare the optional hot water cylinder.
• Procure a motorized 3-way valve (refer to “Control
parts specifications” on page 21 for the details.)
locally and perform piping. Connect the valve cables
to terminals TB05 (7), (8) and (9) of the Hydro Unit.
• Set DIP SW12-1 on the Hydro Unit board to OFF.
(Refer to page 30.)
• Connect the power supply unit for the hot water
cylinder heater to terminals TB03 L and N of the
Hydro Unit.
• Connect cables between the Hydro Unit and the hot
water cylinder as follows:
Hydro Unit terminals TB03 (1), (2), and earth — Hot
water cylinder (1), (2), and
earth
TB06 A, B, and earth — Hot
water cylinder A, B, and earth
22 Hydro Unit
Capacity Setting
0012 = 80*XWH**E
0017 = 140*XWH**E
Factory set but function code
is needed for PCB
replacement or function code
reset procedure has been
completed.
01
–
0012 or
0017
Depends
on Hydro
Unit
23
Second Remote
Controller
Target
temperature
Setting
0=Water temperature
1=Room thermo temperature
40
–
0~1
0
24
Room
Temperature
Sensor Setting
Temperature shift for heating
–
02
-10~10
-1
Temperature shift for cooling
–
03
-10~10
-1
25
Synchronization
control at low
outside
temperature
0 = HP + Boiler
1 = Boiler
2 = Backup heater
5B
–
0~2
0
Location & FC
Number
FC Description
Hydro
RC
Range
Default
After
Commissioning
Change
1
Change
2
36-EN
+00EF99805101_00Ta.book Page 37 Friday, July 2, 2010 4:36 PM
Содержание HWS-1403XWHD6-E
Страница 47: ... 47 EN Hydro Unit Installation Manual MEMO 46 EN ...
Страница 93: ... 93 FR Unité hydroélectrique Manuel d installation NOTES 46 FR ...
Страница 139: ... 139 DE Hydrogerät Installationshandbuch NOTIZEN 46 DE ...
Страница 185: ... 185 SE Hydroenhet Installationshandbok MEMO 46 SE ...
Страница 186: ...EF99805101 ...