Table 5 – Ratings
Items
HCV-7HA
HCV-7HAL
Rated Maximum Voltage
kV
7.2
Rated Operation Voltage
V
1501-6900
Rated Current
A
400
Rated Frequency
Hz
50/60
Interrupting Capacity
kA
7.2
Rated Insulation Level (BIL)
kV
60
Rated Insulation Level (Power-frequency withstand)
kV
18.2
Rated Short-Time Current
kA
6.0 – 1 sec., 2.4 – 30 sec.
Control Voltages*
Vac
100-240
Control Voltages*
Vdc
125-250
Available Rated Trip Voltages
Vdc
N/A
24, 32, 48, 125, 250
Pick-Up Voltage AC or DC (Max.) **
85% Rated (Hot) - 70% Rated (Cold)
Drop-Out Voltage AC or DC (Max.) **
70% Rated (Hot) - 60% Rated (Cold)
Closing time**
msec
50-90
Opening time**
msec
15-40
Arcing time
msec
≤
10
Rated Trip Voltages
Vdc
N/A
24, 32, 48, 125, 250
Minimum Trip Voltages
Vdc
N/A
40-60% Rating
Maximum Trip Current
Adc
N/A
4.8
Method of Operation
Non-latched
Latched
Mechanical Operation
Million
1
0.25
Electrical Operation
Million
0.25
Auxiliary Switch
3 N.O – 3 N.C.
2 N.O. – 2 N.C.
Auxiliary Contact Rating
10 A, 600 V (NEMA Class A600)
Switching Frequency
Times/h
1200
300
*
Adjustable via switch settings on the drive unit
** These are typical values measured under the following conditions:
a) No external devices connected to the mechanism.
b) At sea level.
c) 120Vac control power applied to terminals 1 & 2.
d) Contactor controlled (open/close) via terminals 3 & 4.