Page 20
MAINTENANCE
Table 2 – Check Points for Periodic Inspection (cont.)
Check
Point
Check Item
Check Method
Criteria
What to do
Dielectric
Strength
Measure
main circuit
Measure dielectric
strength between
phases and between
circuits and ground.
22kV AC or 31kV DC for
1 minute
If breakdown occurs,
contact Toshiba.
Open/Close
Operation
----
Perform open/close
operation by electric
operation test to
confirm the correct
operation.
----
If not normal, check
and repair. If
necessary, replace
faulty parts.
Table 3 - Gap/Wipe Standard Values (contactor in new condition)
Parts
Gap Wipe
Allowable
Wear
Normally
energized
type
0.161-0.169 in.
(4.1-4.3 mm)
More than 0.094 in. (2.4 mm) 0.055 in. (1.4 mm)
Vacuum
Interrupter
Latch type
0.161-0.169 in.
(4.1-4.3 mm)
More than 0.087 in. (2.2 mm) 0.047 in. (1.2 mm)
a-contact
0.157
±
0.016 in.
(4
±
0.4 mm)
0.118
±
0.012 in. (3
±
0.3 mm)
b-contact
0.157
±
0.016 in.
(4
±
0.4 mm)
0.118
±
0.012 in. (3
±
0.3 mm)
Auxiliary
Switch
Delayed
b-contact
0.098
±
0.012 in.
(2.5
±
0.3 mm)
0.177
±
0.020 in. (4.5
±
0.5 mm)
----