GX9 ASD Installation and Operation Manual
75
Direct Access Parameter Information
The
GX9 ASD
has the ability to allow the user direct access to the motor control functions. There are two
ways in which the motor control parameters may be accessed from the EOI: Program
Applicable Menu
Path
or Program
Direct Access
Applicable Parameter Number
.
Both methods access the parameter
via the
Program
mode.
Parameters may also be accessed via communications. Once accessed via either means, the parameter may
be viewed or changed.
The
Program
mode allows the user to develop an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the
Program
mode that have user-accessible
Parameter
Numbers
are listed and described below.
The
Direct Access
screen allows for the display of numbers that access hidden parameters that are used by
development personnel. Enable the
Unknown Numbers
field to access these numbers. Contact the
Customer Support Center for information on using the
Unknown Numbers
field.
Note:
Parameter
Settings
are preceded by the number used to select an item if using
communications to write to a parameter location in memory (i.e., F000
0-Disabled, 1-
Enabled).
Note:
Communications setting changes will require that the ASD input power be removed and then
re-applied for the changes to take affect.
Direct Access Parameters/Numbers
Automatic Acceleration/Deceleration
Program
Fundamental
Accel/Decel 1 Settings
This parameter is used to enable acceleration and deceleration rates in
accordance with the applied load automatically.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for
Acceleration Time 1
(
) and
Deceleration
Time 1
(
).
Settings:
0 — Disabled
1 — Enabled
Note:
The motor and the load must be connected prior to selecting
Automatic Acceleration/Deceleration
.
Direct Access Number — F000
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......