GX9 ASD Installation and Operation Manual
191
Earth Fault Alarm Level
Program
Special
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Alarm
activation criteria.
Direct Access Number — F640
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 0
Maximum — 100
Units — %
Earth Fault Alarm Time
Program
Special
Earth Fault
In the event that the
Earth Fault Alarm
activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the
Earth Fault Alarm
is
activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F641
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Trip Level
Program
Special
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip
activation criteria.
Direct Access Number — F642
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 0
Maximum — 100
Units — %
Earth Fault Trip Time
Program
Special
Earth Fault
In the event that the
Earth Fault Trip
activation criteria is met, a timer begins
to count down to zero. Upon reaching zero, the
Earth Fault Trip
is activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F643
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Acceleration/Deceleration Frequency Adjustment
Program
Terminal
Analog Input Functions
This parameter
Enables/Disables
the feature that allows for the external
adjustment of the
Base Frequency
. When enabled, either
VI/II
or
RR
may be
used as an input source for the modification of the
Base Frequency
setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F650
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......