GX9 ASD Installation and Operation Manual
187
Low-Current Detection Time
Program
Protection
Low-current Settings
With the
Low-Current Trip
) parameter is enabled, this function sets the
time that the low-current condition must exist to cause a trip.
Direct Access Number — F612
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Units — Seconds
Short Circuit Detection At Start
Program
Protection
Special Protection Parameters
This parameter determines when the system will perform an
Output Short
Circuit
test.
Note:
Selection 3 is recommended for high-speed motor applications.
Because of the low impedance of high-speed motors the
standard-pulse setting may result in a motor malfunction.
Settings:
0 — Check at Every Run
1 — Check at Only Power On or Reset
2 — Never
Direct Access Number — F613
Parameter Type —
Selection List
Factory Default —
Check at Every Run
Changeable During Run —
No
Short Circuit Pulse Run Duration
Program
Protection
Special Protection Parameters
This parameter sets the pulse width of the ASD output pulse that is applied to
the motor during an
Output Short Circuit
test.
Direct Access Number — F614
Parameter Type —
Numerical
Factory Default —
50
Changeable During Run —
No
Minimum — 1
Maximum — 100
Units — µS
Over-Torque Trip Selection
Program
Protection
Over-Torque Parameters
This parameter
Enables/Disables
the
Over-Torque Tripping
function.
When enabled, the ASD trips if an output torque value greater than the setting
of
exists for a time longer than the setting of
.
When disabled, the ASD does not trip due to over-torque conditions.
Note:
A discrete output terminal may be activated when an over-torque
alarm occurs if so configured (see
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F615
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Over-Torque Detection Level During Power Running
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during positive torque. This setting is a percentage of the
maximum rated torque of the ASD.
.
Direct Access Number — F616
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......