GX9 ASD Quick Start Guide
Alarms
lists the alarm codes that may be displayed during operation of the
GX9 ASD
. Each alarm code
listed is accompanied by a description and a possible cause. In the event that the source of the malfunction
cannot be determined, contact your TIC Sales Representative for further information on the condition and
for an appropriate course of action.
The
Alarms
are listed in the top-down order that they are checked for activation. Only the first to be
detected will be displayed on the
Frequency Command
screen.
Note:
Some
User Notification
conditions and
Alarms
may be annunciated via a discrete
output terminal setting. See the GX9 ASD Installation & Operation Manual for a listing
of the possible system conditions that may be associated with an output terminal.
Table 7. GX9 ASD Alarms.
LED
Screen
LCD
Screen
Description
Possible Causes/
Troubleshooting
CM1
Communication Error
(scan error)
Internal communications error.
• Improperly programmed ASD.
• Improper communications settings.
• Improperly connected cables.
CM2
Communication alarm
2 (RS232/RS485/TTL
error)
External communications error.
EF
Earth Fault
Active ground fault.
• Ground fault at the motor.
• Ground fault at the output of the ASD.
• Current leakage to
Earth Ground
.
EFU
DC Fuse Open
Incorrect current reading at DC
fuse circuit.
• Open circuit at DC bus circuit.
ERR1
Point Setting Error
Incorrect setup at an analog
input (e.g., VI/II, RR, etc.).
• Gain and bias settings for an analog input are
either the same or too close to each other (e.g.,
F201
and
F203
are equal).
LOd
PID Low Output
Disable
LOD function enabled and the
output frequency is less than the
F732
setting.
• Disable the
LOD
function at
F731
or increase the
Low Output Disable Start Level
at
F732
.
MOFF
Main Power Under-
Voltage
Under-voltage condition at the
3-phase AC input to the ASD.
• Low 3-phase commercial voltage.
OC
Over-Current
ASD output current greater than
F601
setting.
• Defective IGBT (U, V, or W).
• ASD output to the motor is connected incorrectly.
• ASD output phase-to-phase short.
• The ASD is starting into a spinning motor.
• Motor/machine jammed.
• Mechanical brake engaged while the ASD is
starting or while running.
• Accel/Decel time is too short.
• Voltage Boost setting is too high.
• Load fluctuations.
• ASD operating at an elevated temperature.
Содержание GX9 ASD
Страница 1: ...GX9 ASD Quick Start Guide TOSHIBA GX9 ASD Quick Start Guide DN 66900 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66900 001 March 2014 GX9 ASD Quick Start Guide ...
Страница 4: ......
Страница 88: ...78 GX9 ASD Quick Start Guide Figure 33 GX9 ASD 5 0 20 HP Enclosure ...
Страница 89: ...GX9 ASD Quick Start Guide 79 Figure 34 GX9 ASD 25 75 HP Enclosure ...
Страница 90: ...80 GX9 ASD Quick Start Guide Figure 35 GX9 ASD 100 200 HP Enclosure ...
Страница 91: ...GX9 ASD Quick Start Guide 81 Figure 36 GX9 ASD 250 400 HP Enclosure ...
Страница 92: ...82 GX9 ASD Quick Start Guide Figure 37 GX9 ASD 500 800 HP Enclosure ...
Страница 93: ...GX9 ASD Quick Start Guide 83 Figure 38 GX9 ASD 900 1200 HP Enclosure ...
Страница 99: ......