6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 939 -
(v)
Logic level inversion
The logic inversion function can invert the input signal for each binary output circuit; the user
can invert an input output when the user sets
Inverse
for the scheme switch [
INVERSE-SW
].
Normal
setting is also provided when logic inversion is not required for processing.
(vi)
Logic timer switch
In order that the binary output circuit can have a programmable reset characteristic, a scheme
switch and a setting are provided. The programmable reset characteristic consists of four types
and the user can select the type required using a scheme switch: (1) dwell type, (2) delay type,
(3) latch type, and (4) instantaneous type:
Instant type
When the user uses a binary output signal without the following characteristics, the user
should set
Off
for the scheme switch [
TIMER-SW
].
Delay type
If the user requires a binary output signal with a delayed characteristic, the user should set
Delay
for scheme switch [
TIMER-SW
] and set the value of the pulse width using setting [
Logic
timer
].
Dwell type
For instance, if the user requires a binary output signal as a one shot pulse, the user should
set
Dwell
for scheme switch [
TIMER-SW
] and set the value of the pulse width using setting
[
Logic timer
]. If the input signals received have a shorter duration than the set value in the
setting [
Logic timer
], the pulse width will be equal to the setting value. On the other hand, if
the duration of the input signals are longer than that of the set value, the pulse width will be
equal to the width of the input signals.
Latch type
If the user requires a binary output signal to be removed by a reset signal, the user should set
Latch
for scheme switch [
TIMER-SW
] and key the Data ID of the reset signal for setting [
Reset
signal
]. Since the binary output signal is removed with the Data ID, the user should determine
the Data ID from other functions. The Data ID is designated by the signal monitoring point for
each function and the user should set the [
Reset signal
] setting.
Note: When
Latch
is set, the state of BO circuit will be sustained during power turn-
on/off.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......