6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 936 -
5.4.4
Binary output circuit
Either a CPL logic or a PLC signal can drive a binary output circuit. Table 5.4-9 shows the
settings summary of CPL function.
Table 5.4-9 Setting items for binary output circuits
Setting items
Setting-range or
Data_ID
Uni
t
Contents
Default
BO1_CPL
Off / On
– Switch On for programmable operation
Off
BO1
Input signal1
(Preferred Data ID)
– Set a Data ID at the first input on BO1.
Not assigned
1
Input signal2
(Preferred Data ID)
– Set a Data ID at the second input on BO1.
Not assigned
1
Input signal3
(Preferred Data ID)
– Set a Data ID at the third input on BO1.
Not assigned
1
Input signal4
(Preferred Data ID)
– Set a Data ID at the forth input on BO1.
Not assigned
1
Input signal5
(Preferred Data ID)
– Set a Data ID at the fifth input on BO1.
Not assigned
1
Input signal6
(Preferred Data ID)
– Set a Data ID at the sixth input on BO1.
Not assigned
1
Input signal7
(Preferred Data ID)
– Set a Data ID at the seventh input on BO1.
Not assigned
1
Input signal8
(Preferred Data ID)
– Set a Data ID at the eighth input on BO1.
Not assigned
1
LOGIC-SW
AND/OR/XOR
– Switch for logic-gate operation on BO1
AND
On Delay Timer
0.000 to 300.000
s Set a value for an on-delay-timer on BO1
0.000
Off Delay Timer
0.000 to 300.000
s Set a value for an off-delay-timer on BO1
0.000
INVERSE-SW
Normal / Inverse
s Inversion operation of BO1 signal
Normal
TIMER-SW
OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO1
OFF
Logic Timer
0.000 to 300.000
s Setting Off Delay Timer for Delay and Dwell
0.000
Reset signal
(Preferred Data ID)
– Setting Data ID for Latch
Not assigned
1
BO2_CPL
Off / On
– Switch On for programmable operation
Off
BO2
Input signal1
(Preferred Data ID)
– Set a Data ID at the first input on BO2.
Not assigned
1
…..
…..
…..
…..
Input signal8
(Preferred Data ID)
– Set a Data ID at the eighth input on BO2
Not assigned
1
LOGIC-SW
AND/OR/XOR
– Switch for logic-gate operation on BO2
AND
On Delay Timer
0.000 to 300.000
s Set a value for an on-delay-timer on BO2
0.000
Off Delay Timer
0.000 to 300.000
s Set a value for an off-delay-timer on BO2
0.000
INVERSE-SW
Normal / Inverse
– Inversion operation of BO2 signal
Normal
TIMER-SW
OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO2
OFF
Logic Timer
0.000 to 300.000
s Setting Off Delay Timer for Delay and Dwell
0.000
Reset signal
(Preferred Data ID)
– Setting Data ID for Latch
Not assigned
1
…..
BO
n
_CPL
Off / On
– Switch On for programmable operation
Off
BO
n
Input signal1
(Preferred Data ID)
– Set a Data ID at the first input on BO
n
Not assigned
1
…..
…..
…..
…..
Input signal8
(Preferred Data ID)
– Set a Data ID at the eighth input on BO
n
Not assigned
1
LOGIC-SW
AND/OR/XOR
– Switch for logic-gate operation on BO
n
AND
On Delay Timer
0.000 to 300.000
s Set a value for an on-delay-timer on BO
n
0.000
Off Delay Timer
0.000 to 300.000
s Set a value for an off-delay-timer on BO
n
0.000
INVERSE-SW
Normal / Inverse
– Inversion operation of BO
n
signal
Normal
TIMER-SW
OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO
n
OFF
Logic Timer
0.000 to 300.000
s Setting Off Delay Timer for Delay and Dwell
0.000
Reset signal
(Preferred Data ID)
– Setting Data ID for Latch
Not assigned
1
1
Note: The user can set a reset signal and eight input signals with Data IDs. Data IDs
are listed as a signal monitoring point for each function. Setting items are
summarized in each slot. (See sections 5.4.8(i) and 5.4.8(ii))
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......