6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 882 -
Table 4.11-11 Mapping signals for SPCSO1 object
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GAPC1$SPCSO1$origin
orCat
orCategory
ST
523001 300D011008
ASEQ01_ORCAT
Ctrl/GAPC1$SPCSO1$origin
orIdent
Octet64
ST
523001 6A0D011009
ASEQ01_ORIDENT
Ctrl/GAPC1$SPCSO1
stVal
BOOLEAN
ST
523001 000D011001
ASEQ01_ACC_EXEC
Ctrl/GAPC1$SPCSO1
q
Quality
ST
523001 310D011005
ASEQ01-QUALITY
Ctrl/GAPC1$SPCSO1
t
Timestamp
ST
523001 900D011006
ASEQ01_TIME
Ctrl/GAPC1$SPCSO1
stSeld
BOOLEAN
ST
523001 000D011D90
ASEQ01_STSELD
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Drag and drop
Figure 4.11-8 orCat attribute mapped into SPCSO1 object of GAPC1
(iii)
Mapping input data
The ASEQ1 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “ASEQ01_CONTROL_REQ”. Table 4.11-12 shows the input-point
“
ASEQ01_CONTROL_REQ” and the Object reference “Ctrl/GAPC1$SPCSO1”; the user should
map the input-point to the Object references with
attributes CO and CF under FC†. Figure 4.11-9
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......