6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 866 -
when the GENBI function determines that the signal is being generated repetitively.
Event No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
D
E
B
On
On
On
On
On
On
On
On
[
GBI-TELD
]
[
GBI-TELR
]
Event suppression
Time.................
Signal
from
device
C
Figure 4.10-3 Example of signals and events suppressed by setting
Figure 4.10-3 illustrates the case where a device produces repetitive signals. From this
figure, it can be seen that the start of event suppression occurs at the tenth state-change (point
B) because the GENBI function counts the number of state-changes. The GENBI function
detects the commencement of the signal repeated from the signal initiation point ‘A’. Scheme
switch [
GBI-NELD
] is provided to set the number of state-changes so that this function will
start to suppress the signal from this point. The user can set [
GBI-TELD
] pertaining to the
detection period of the repetitive signals (point A to point C). For example, the user can set the
value “10” for the scheme switch [
GBI-NELD
]; period A–C is set for the setting [
GBI-TELD
].
The GENBI function should remove event suppressed operation when the repetitive
signals disappear, (that is, the operation of the device is steady); event suppression operation
is cleared when no repetitive signal is found for a set period. The user can set the period using
scheme switch [
GBI-TELR
]; this reset operation clears the event suppression function at point
E when the last state change is confirmed at point D. Here, the period D–E is set for the Scheme
switch [
GBI-TELR
].
The event suppression function is provided for every device; the user should set
On
for
the scheme switch [
SLOT1 GBI01-SPPEN
], for example.
Table 4.10-2 Example of event list screened
Event
Event contents screened
Off
No.1 event
On
No.2 event
Off
No.3 event
On
No.4 event
Off
No.5 event
On
No.6 event
Off
No.7 event
On
No.8 event
Off
No.9 event
On
No.10 event suppression SET
On
Event suppression RESET
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......