6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 758 -
4.8.4
Operation counter
The DPOS01 function has an operation-counter†; the user can utilize the operation-counter to
predict the lifespan of switchgear and other functions. The user can select a count mode using
a setting. Table 4.8-22 and Figure 4.8-32 show the modes, for which a user is required to change
a mode in response to a device signal. For instance for the DPOS01 function, a user can select
the mode using scheme switch [
DPOS01-CNTS
], which is set to
C-On
; counting-up is performed
when a switchgear signal gives rise to a change in state from “Off to On”.
Table 4.8-22 Mode of operation counter
Mode
Description
C-On
Counting-up is performed when a signal changes to closed (On). When the signal
is changed from “Off to On”, the counter value is incremented.
C-Off
Counting-up is performed when a signal changes to open (Off). When the signal
is changed from “On to Off”, the counter value is incremented.
C-OnOff
Counting-up occurs when any state change occurs: that is, “Off to On” or “On to
Off”.
NA
Stop the count function
†Note: The operation-counter value is not cleared when power is removed from the IED.
The operation-counter is available in the DPOS01 to DPOS72 functions.
On state
Off state
Figure 4.8-32 Device signal
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See chapter
User interface: Monitoring sub-menu
.
DPOS1-CNT1
10:48
1/4
DPOS_Dev1-3Ph +
0
DPOS_Dev1-APh +
0
DPOS_Dev1-BPh +
Operation Counter
10:48
1/25
DPSY1-CNT
>
DPSY2-CNT
>
_DPOS1-CNT
>
DPOS2-CNT
>
DPOS3-CNT
>
DPOS4-CNT
>
ENTER
CANCEL
Figure 4.8-33 Operation counter sub-menu
Note: With regard to signal “DPOS01_3PH_STATE”, the sub-menu represents it as
“DPOS_Dev1-3Ph”. Analogous to the signal “DPOS01_3PH_STATE”,
“DPOS01_APH_STATE” is represented as “DPOS_Dev1-APh”. Signals
“DPOS01_BPH_STATE” and “DPOS01_CPH_STATE” are displayed in a similar
manner.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......