6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 577 -
DPSY01 function (Function ID: 511001)
S
R
0.1
– 50.0 s
[
DPSY01-CPW
]
PLC
ILK condition (“Closing”) passed
DPSY01-Close
“DPSY01_OEC_OK_CSF”
(511001 8002011E7F)
&
&
1
≥
1
≥
1
≥
&
&
Input
Output
Operate logic in DPSY01
“DPSY01_OEC_OK_CS”
(511001 8102011E82)
Operate Command
with ILK
†
condition
Operate Command
without
condition
&
Operate Command
with ILK
†
condition & synchro-checking
Operate Command
with
synchro-checking
&
Assign to BOs
Operate condition
‡
[
DPSY01-LGCTRCON
]
Fixedlogic
Fixedlogic
[
DPSY01-LGCFEXOT
]
DPSY01IN_TMP_35
511001 810201EE57
User configurable condition
(PLC#1 connection point)
&
&
“DPSY01_OEX_BO”
§§
(511001 8202011DD3)
To BO connection
[
DPSY01-PLSM
]
*
Var
Fix
Operate Failed
[
DPSY01-RST
]
ASEQ function
” is in progress
ASEQ_MULTI_SEL
“DPSY01_OEC_OK_CSF”
(511001 8002011E7F)
“DPSY01_EX_FFL”
‡‡
(511001 8602011E91)
To
“Wait for a command”
&
&
DPSY01IN_TMP_44
511001 820201EE5E
User configurable condition
(PLC#2 connection point)
1
≥
&
“DPSY01_EX_CMP”
(511001 8002011E93)
Operate Completed
1.0s- 100.0s
0
t
DEV01_CL_SYNC_INTER
511001 800201EE35
Closing control command with ILK
†
and synchro checks
(PLC#1 connection point)
DEV01_CL_SYNC
511001 800201EE34
Closing control command with synchro check
(PLC#2 connection point)
DEV01_CL_INTERLOCK
511001 800201EE33
Closing control command
with interlock check
(PLC#3 connection
point)
DEV01_CL_COMMAND
511001 800201EE32
Closing control command with no check
(PLC#4 connection point)
From SYNCHK
SYNC01-SYN_CLC
(560001 850B011F59)
S
R
Detection of state-change in
a device
“DPSY01_EX_CMP”
(511001 8002011E93)
Figure 4.2-28 Closing operation logic with PLC in DPSY01
††
†Note: The ILK function can provide the criteria for operation for “Closing” control.
‡Note: An “operate condition” signal is generated in the operate-condition logic (see
Fixlogic
is set for scheme switch [
DPSY01-LGCTRCON
]. If an
alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operated-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 1.10-28 using
connection point #1 “User-configurable condition”. That is, set the scheme switch
[
DPSY01-LGCTRCON
] to
PLC
and use “DPSY01IN_TMP_35”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when
Fixlogic
is set for scheme switch
[
DPSY01-LGCFEXOT
]. If the signal to be issued from the logic programmed by the
user instead of the logic shown in Figure 4.2-20, connect the signal “Operate
completed” generated in the user-programmed logic to connection point #2 “User
configurable condition”. That is, set the scheme switch [
DPSY01-LGCFEXOT
] to
PLC
and use “DPSY01IN_TMP_44”.
*Note: The user can set the type of output signal. When
Var
is set for scheme switch
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......