6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 300 -
2.20.1
Overcurrent element (OCFS)
Three overcurrent elements consist for the three-phases: OCFS-A, OCFS-B, and OCFS-C.
Their pick values of those elements are determined by a setting [
OCFS
]. Those element can
operate when
On
is set for scheme switch [
OCFS-EN
].
2.20.2
Phase current change detector element (OCDFS)
Three elements consist for three-phases and they are used to detect changing currents per
phase: OCDFS-A, OCDFS-B, and OCDFS-C. Figure 2.20-1 shows that those elements operate
if vectorial differences (between currents I
M
and I
N
) are being observed in a cycle, and their
differences are larger than setting [
OCDFS
]. Because the quiescent load current does not affect
the operating sensitivity of OCDFS elements, they can detect a fault current precisely.
I
s
I
M
I
N
Figure 2.20-1 Current change detection
They can operate based on the following equation.
|𝐼
𝑀
− 𝐼
𝑁
| ≥ 𝐼
𝑆
(2.20-1)
where,
IM = present current
IN = current one cycle before
Is = setting [
OCDFS
]
Those settings are determined by a setting [
OCDFS
], and those elements can operate when
On
is set for its scheme switch [
OCDFS-EN
]. They, additionally, have off-delay timers. A setting
[
TOCDFS
] is provided to adjust those timers.
2.20.3
Earth fault current element (EFFS)
Residual current is measured in an earth fault current element, so an earth fault is detected
if the residual current gets over a setting level [
EFFS
]. Its elements can operates when
On
is
set for the scheme switch [
EFFS-EN
].
If its earth fault current is significant, because of unbalance in the network,
Off
should
be set for that [
EFFS-EN
] to disable the operation of the EFFS.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......