6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 213 -
2.8.2
Thermal characteristic
THM characteristics are determined with two equations. Equation (2.8-3) is used to define the
cold state. Equation (2.8-4) is used to define the hot state:
t = τ ∙ Ln [
𝐼
2
𝐼
2
− 𝐼
𝐴𝑂𝐿
2
]
(2.8-3)
t = τ ∙ Ln [
𝐼
2
− 𝐼
𝑃
2
𝐼
2
− 𝐼
𝐴𝑂𝐿
2
]
(2.8-4)
where t is time to trip for a constant overload current of I (minutes), I is the overload current
(largest phase current in amperes), I
AOL
is the permitted overload current (amperes), Ip is the
pre-load current (amperes), τ is the thermal time constant (minutes), and Ln is the natural
logarithm.
In Equation (2.8-3), cold curves are special versions of the hot curves where Ip is zero,
catering for the situation where a cold system is switched onto an immediate overload.
Figure 2.8-1.a shows the cold state where an overload has been switched onto a previously
un-loaded system. Figure 2.8-1.b shows the hot state where an overload is switched onto a
system that has previously been loaded to 90% of its capacity. The figures are in conformity
with the IEC 60255-149 curves, and these curves are drawn in a range of settings of the time
constant (
).
a.Thermal Curves (Cold Curve - no prior load)
b. Thermal Curves (Hot Curve - 90% prior load))
100
50
20
10
5
1
Figure 2.8-1 Thermal curves
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......