6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 183 -
(vi)
Reset time of DT
In the DT characteristic, the reset time is designed to be instant.
(vii)
Summary of EF operation
Table 2.6-4 shows a summary for EF operation. Note that
DEF
will be set unconditionally in
IEC-NI, VI, EI and UK-LTI characteristics (†).
Table 2.6-4 Type and standard board in the EF (A tick represents a selectable function)
Characteristics
DT
IDMT
IEC-NI
IEC-VI
IEC-EI
UK-LTI
IEEE-MI
IEEE-VI
IEEE-EI
US-CO2
US-CO8
Original
Scheme
sw
itch
[
EF
1
-T
im
er
]
DT
IEC-NI
✓
IEC-VI
✓
IEC-EI
✓
UK LTI
✓
IEEE-MI
✓
IEEE-VI
✓
IEEE-EI
✓
US-CO2
✓
US-CO8
✓
Original
✓
Scheme
sw
itch
[EF
1
-Rt
imer
]
DEF
N.A
✓
†
✓
†
✓
†
✓
†
✓
✓
✓
✓
✓
✓
DEP
N.A
✓
N.A
✓
N.A
✓
N.A
✓
N.A
✓
N.A
✓
2.6.3
Threshold level for operation
The value of threshold current at which the EF (I
EF
) element will pick-up is configured by a
setting; the setting [
EF1
] is provided for both the IDMT and the DT characteristic. Note that
the settings of the threshold levels are allowed to have distinct values in the respective EF
elements. A rating current for the input is defined either 1A or 5A; the input rating is defined
on a VCT. (For more information about the VCT, see Chapter
Technical description:
Transformer module for AC analogue input
).
2.6.4
Reset Ratio
The ratio of the threshold current for pick-up to reset is applied using a setting; for example,
the ratio for the EF1 element is set using the setting [
EF1-DPR
]. The reset ratios for the other
EF elements are also provided.
2.6.5
Miscellaneous functions
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......