6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 180 -
Figure 2.6-3 IDMT Characteristics curves
(iv)
Operate time of DT
The operate time in the DT is a constant.
Time characteristic
The user should set
DT
for the scheme switch [
EF1-Timer
]. The value of the required operate
time is set for the setting [
TEF1
] in the range 0.00–300.00s.
Instantaneous activation
The instantaneous operation characteristic is achieved by setting zero for the [
TEF1
], but the
instantaneous one can be also obtained when the logic signal ‘1(High)” is programmed to be
injected at the PLC connection point “EF1_INST_OP”.
(v)
Reset time for IDMT
Programming the reset time characteristic is available for the IEEE standard, US standard
and original (user-programmable) inverse-time-reset characteristic†. In the IEEE standard,
for example, the user can set
DEP
for the scheme switch [
EF1-Rtimer
]. The following equation
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......