6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 164 -
the scheme switch [
OC1-OPMD
]. Conversely, when a trip is only required for faults that occur
in two or more phases,
2OUTOF3
(a fault occurs in two or more phases) is set for the scheme
switch [
OC1-OPMD
].
Table 2.5-6 Fault type and tripping mode
Fault type
Setting [
OC1-OPMD
]
Phase-A
Phase-B
Phase-C
3POR
2OUTOF3
X
–
–
✓
No trip
–
X
–
✓
No trip
–
–
X
✓
No trip
X
X
–
✓
✓
–
X
X
✓
✓
X
–
X
✓
✓
X
X
X
✓
✓
Note: A tick (
✓
) indicates that a trip is issued when faults are detected.
A mark (X) indicates the occurrence of a fault on a particular phase. A mark
shown thus (–) indicates that no fault has occurred on that particular phase.
(ii)
Blocking OC by ICD
The operation of each OC element can be blocked if the ICD function detects a second
harmonic current caused by the magnetizing inrush current phenomenon when a
transformer is energized. For example, for the OC1 element, the scheme switch [
OC1-
2fBlk
] is provided, and
Block-3P
should be set when the user wishes to block all three-
phases of the OC1 element when the second harmonic associated with the magnetizing
inrush current is present. Alternatively,
Block-PerP
is set if blocking is just required for a
single phase concerting to the phenomenon.
Non
is set for the scheme switch [
OC1-2fBlk
]
as the default setting. For more information about the ICD function, see Chapter
Relay
application: Inrush current detection function
.
(iii)
Blocking OC by VTF
The operation of the OC element can be blocked by the voltage transformer failure (VTF)
function via a scheme switch. For example,
Block
can be set for the scheme switch [
OC1-
VTFBlk
] to block the operation of the OC1 element during a VTF condition.
Non
is set for
the scheme switch [
OC1-VTFBlk
] as a default. For more information about the VTF, see
Chapter
Relay application: VT failure detection
.
(iv)
OC operation for auto-reclose
The OC element activates the auto-reclose (ARC) function. However, if for example ARC
is not required,
Block
is set for the scheme switch [
OC1-ARCBlk
].
Block
is set for the
scheme switch [
OC1-ARCBlk
] as a default.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......