6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 153 -
2.5.1
Relay polarity
The user can choose either non-directional OC or directional OC for each OC stage. In addition,
the user can further select either the forward or the reverse direction for each of the directional
OC elements selected.
(i)
Characteristic of non-directional OC
The characteristic of the non-directional type OC is a circle that has a center at the origin. A
setting and a scheme switch is used to configure each non-directional OC element; i.e., the user
can set the threshold value of the non-directional OC element for stage 1 using setting [
OC1
],
provided time characteristic is required for define time delay (DT) described in section 2.5.2(ii).
Nondir
should be set for the scheme switch [
OC1-Dir
].
(ii)
Characteristic of directional-OC element in the forward direction
As shown in Figure 2.5-1, the characteristic of the directional-OC elements in the forward
direction is a semi-circle based upon the border-line; the hatched area shows the operating
region of a directional-OC element.
Figure 2.5-1 Characteristic of the directional-OC element in the forward direction
1
Note: Directional characteristic angle (θ) forms the angle between the reference
quantity and the directional characteristic angle line. The half plane represents
the zone of operation bordered on one side by the border line and extending in the
direction that contains both the reference (polarizing) and operating quantities.
2
Note: For the polarizing voltage (Vpol), greater than 1.0 voltage should be applied for
sensing.
A reference signal, that is, a polarization signal is required by the directional OC element,
the reference signal is derived from a phase-to-phase voltage: for example, the directional OC
Reference voltage or
Polarizing voltage
2
(Vpol)
Operation (Trip) zone
I
Non-operation (No trip) zone
θ
1
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......