6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1328 -
(ii)
GOOSE receiving block (GOSUBBLK)
This is used for receiving or rejecting GOOSE subscription information from another IED for
testing bad reception. See Chapter
Communication protocol: IEC 61850 communication
.
(iii)
Test flag cancel (S-TestFlagCancel)
Test flag in the communication packet will be removed unconditionally, when
On
is set for
setting [
Test flag
].
(iv)
Test for all communication (TestFlag-EN)
Setting [
TestFlag-EN
]=
On
allows to set test flags at all communication protocol (see Chapter
User interface: Test-submenu
).
14.4.2
Test for relay application
(i)
Auto monitoring function (A.M.F)
Issuing alarms will be blocked when
Off
is set for [
A.M.F
]. For the content about the monitoring
function, see Chapter
Automatic supervision function
.
(ii)
Test of cold load protection (CLP-Test)
STATE0 or STATE3 will be selected temporally, if
STATE0
or
STATE3
is set for setting [
CLP-
TEST
]. See Chapter
Relay application: Cold load protection
for more detail.
(iii)
ZS, ZG test (ZS-Test.CTRL, ZS-Offset.CTRL, ZS/ZG-Test.XAngle)
ZS-Test.CTRL
Setting [
ZS-Test.CTRL
]=
On
allows not to operate Zmin feature. For more information about
the Zmin, see Chapter
Relay application: Distance protection
.
ZS-Offset.CTRL
Setting [
ZS-Offset.CTRL
]=
Non-Offset
allows not to operate offset feature during the test.
ZS-Test.XAngle, ZG-Test.XAngle
Setting [
ZS-Test.XAngle
]=
On
allows to take fixed knee characteristic during the test.
(iv)
Thermal overload function test (THM-Test, THM-IP)
Setting [
THM-Test
]=
On
allows to have a test value for the pre-load current (Ip). The Ip value
is discussed in Chapter
Relay application: Thermal overload function
.
(v)
SOTF test (SOTF-Test)
Setting [
SOTF-Test
]=
On
allows to generate the cold load condition mandatorily for testing,
which is discussed in Chapter
Relay application: Switch on to fault
.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......