Monitoring sub-menu
“Monitoring” sub-menu is used to display the current status of the IED. The data is updated
every second on the LCD screen. The user can view the following functions from the Monitoring
sub-menu:
i.
Metering sub-menu
ii.
Binary I/O sub-menu
iii.
Communication sub-menu
iv.
Relay Elements sub-menu
v.
Statistics sub-menu
vi.
GOOSE Monitoring sub-menu
vii.
Diagnostics sub-menu
(i)
Metering
The value and direction of current, voltage etc. can be displayed. The user can change the units
as required by using the appropriate setting. Figure 12.4-1 shows an example of the Metering
sub-menu.
Figure 12.4-1 Display for Metering
(ii)
Binary I/O
“Binary I/O” sub-menu can be used to display the respective status of the binary IO module
circuits. The LCD displays the binary input or output signal number, the signal name
1
assigned to the circuits of the binary IO modules and their status in a line. The status for the
binary output circuit is shown by a logic level (“1” or “0”). Figure 12.4-2 provides an example
for binary IO module at IO#1 (Slot#1).
Figure 12.4-2 Display of Binary I/O status
1
Note: The user can set the names of binary signals with GR-TIEMS.
Metering
10:48 1/25
V
a
23.231kV 121.34deg
Vb
23.200kV 120.14deg
Vc
22.713kV 121.50deg
Slot#1
10:48 1/12
B
I1 0 CB1 contact
BI2 0 DC power sup.
BI3 0 Trans-T Comm1
BI3 0 Trans-T Comm2
BI4 0 ARC-Block1
BI5 0 Indi. Reset
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......