6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1200 -
Table 11.3-9 GOOSE statutes and signal outputs
Signal values
LCD screen messages
GR-TIEMS screen messages
0x0000
OK
GOOD
0xC000
NG
QUESTIONABLE
0xC010
NG
QUESTIONABLE | TEST
0xC040
NG
QUESTIONABLE | INACCURATE
0xC080
NG
QUESTIONABLE | INCONSISTENT
When the user wishes to see GOOSE outputs†, the user can see them by user’s PLC logic, but
the user should build its logic using the PLC function. Table 11.3-10 shows the GOOSE signals,
which the user can select. For example, in order to get the GRL200_Bay1_4 information, the
user should take the GOOSE content using SUB_QUAL#3 output.
Table 11.3-10 GOOSE output signals
Data ID
Signal names
Descriptions
301101 3100001001 SUB_QUAL#0
GOOSE subscription quality status
301101 3100011001 SUB_QUAL#1
GOOSE subscription quality status
301101 3100021001 SUB_QUAL#2
GOOSE subscription quality status
301101 3100031001 SUB_QUAL#3
GOOSE subscription quality status
301101 3100041001 SUB_QUAL#4
GOOSE subscription quality status
~~~
~~~
~~~
301101 31013E1001 SUB_QUAL#318 GOOSE subscription quality status
301101 31013F1001 SUB_QUAL#319 GOOSE subscription quality status
†Note: The user cannot view GOOSEs signal lists on the GR-TIMES engineering.
11.3.9
Feature of IEC61850 Edition1 option
The IED can have Private logical nodes, which are provided in Editon1_option, which are
designed in Toshiba private specification exclusively. The user can select and add the following
Data object:
Table 11.3-11 LD class in Editon1 option
LD Class
DO
Content
GGIO
AnInDatUpd
DataUpdate Trigger is provided for general Data
Object. The structure is the same as AnIn.
Note: The option1 is designed to transfer the metering values during the fault on the
IEC61850 Edition1.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......