G2020 Series UPS Installation and Operation Manual
– 94861-004
These contacts can be programmed to provide any of the functions shown in Table 4-2. The default programmed
values are indicated with an asterisk (*).
Table 4-2 External Output Functions
Code
Function
Description
0
NONE
1 *
TOTAL ALARM
Summary alarm; activated when any minor, major, fault or alarm has occurred with the
system.
This is the default setting on OUT8.
2
MINOR FAULT
Activated when a minor fault has occurred with the system.
3
ALARM
Activated when an alarm has occurred with the system.
4
AC INPUT ABNORMAL
Activated when the input voltage or frequency is abnormal.
5
BYPASS ABNORMAL
Activated when the bypass voltage or frequency is abnormal.
6
BATTERY ABNORMAL
Activated when the battery is abnormal.
7
BATTERY LOW VOLTAGE 1
Activated when the battery voltage drops below Discharge Warning Voltage Level 1 during
inverter operation. This level is set in the TEST MENU by an Authorized Toshiba Service
Provider.
8 *
BATTERY LOW VOLTAGE 2
Activated when the battery voltage drops below Discharge Warning Voltage Level 2 during
inverter operation. This level is set in the TEST MENU by an Authorized Toshiba Service
Provider.
This is the default setting for OUT5.
9
BATTERY DEPLETION
Activated when the battery voltage drops below discharge end voltage level during inverter
operation.
10 *
OVERLOAD
Activated when an overload of 105% or more had occurred to the system.
This is the default
setting on OUT6.
11
OVERLOAD PREALARM
Activated when the load goes over 100%. This level is adjustable by an Authorized Toshiba
Service Provider.
12
FAULT GROUP 1
Activated when the preset group of alarms (Fault Group 1) all occur to the system at once.
These groups are set in the TEST MENU by an Authorized Toshiba Service Provider.
13
FAULT GROUP 2
Activated when the preset group of alarms (Fault Group 2) all occur to the system at once.
These groups are set in the TEST MENU by an Authorized Toshiba Service Provider.
14
BYPS. SYNCHRONOUS
Activated when the inverter voltage and bypass voltage are synchronous.
15
BYPS. ASYNCHRONOUS
Activated when the inverter voltage and bypass voltage are asynchronous.
16
REMOTE OPE. ENABLE
Activated when any remote operation occurs (Stop/Start Inverter, etc.)
17 *
LOAD ON INVERTER
Activated when the power is supplied from the inverter.
This is the default setting on OUT2.
18 *
LOAD ON BYASS
Activated when the power is supplied from the inverter.
This is the default setting on OUT1.
19
LOAD ON AC
Activated when the power is supplied from the input via the UPS's rectifier/converter -
inverter.
20 *
BATTERY OPERATION
Activated when the battery is operating following an AC power failure.
This is the default setting on OUT3.
21 *
CONVERTER OPERATION
Activated when the converter is operating.
This is the default setting on OUT4
22
INVERTER OPERATION
Activated when the inverter is operating.
23
CB1 CLOSE
Activated when CB1 (Input Contactor) is closed.
24
CB2 CLOSE
Activated when CB2 (Battery Breaker) is closed.
25
52S CLOSE
Activated when 52S (Bypass Contactor) is closed.
26
POWER DEMAND ON
Activated when a Power Demand is activated by one of the Inputs.
27
EQUALIZING CHARGE
Activated when the UPS is charging the batteries at the equalizing charge level. This
command boosts the charge voltage (500-640 V) for a preset duration (0-100 hr.)
28
ANOTHER BUS SYNC.OK
Annunciates that the UPS is successfully synchronized to an external source
*Default output settings