SPECIFICATIONS
ANALOG INPUTS
ITEM
SPECIFICATION
Part Number:
See Order Numbers Below
I/O Registers Assigned:
None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)
Input Range: Thermocouple
Resolution
J, K, R, S, T, E, N, & B . 0-100 mV, Cold Junction Compensation Error
1
°
maximum, 0.5
°
C typical.
Input Range: RTD
Resolution
PT100 (0.00395 and 0.00385), 3 Wire Compensation, Current Sense
0.5ma. Range: -200
°
to 800
°
C
Input Range: Voltage
Current
Resolution
0-100 mV, 0-10 V (via PLC scaling/external shunt resistor)
0-20 mA
12 bit
ANALOG OUTPUTS
ITEM
SPECIFICATION
Part Number:
See Order Numbers Below
I/O Registers Assigned:
None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)
Output Range: Voltage
Current
0-10 V, Minimum Load = 400
Ω
4-20 mA Maximum Load = 500
Ω
GENERAL
ITEM
SPECIFICATION
Communication Ports: PLC
IBM
Connects to T1 Programming Port
Connects to Computer for Setup Connects to OIS for PLC Access
Temperature:
Operating: 0
°
to 50
°
C Storage: -25
°
to 80
°
C
Humidity:
10% to 90% Non condensing
Immunity to ESD:
Level 3 per IEC 61000-4-2
Immunity to Transients:
Level 3 per IEC 61000-4-4
Radiated Susceptibility:
Level 3 per IEC 61000-4-3
Emissions:
EN55011 CISPR A
Certifications:
CE, CSA
Isolation:
Analog isolated from Digital, no isolation between channels.
Size
Eagle 0800 & 0404 155mm x 102mm x 48mm
Eagle 0201 94mm x 42mm x 47 mm
Mounting:
DIN rail or through hole
Weight
Eagle 0800 & 0404: 0.5 kg Eagle 020:1 02 kg
ORDER NUMBERS
ITEM
DESCRIPTION
Eagle0201U
2 Universal Analog Inputs, 1 Analog Output.
Eagle0404U
4 Universal Analog Inputs, 4 Analog Outputs.
Eagle-0800U
8 Universal Analog Inputs.
TKEAGLE05T1
Cable, 50 cm, Connects T1 to Eagle Exp.Unit
TKEAGLE20T1
Cable, 2 m, Connects T1 to Eagle Exp.Unit1
TKEAGLE20T2
Cable, 2 m, Connects T2 to Eagle Exp.Unit
NOTES: 1. Each Eagle unit contains setup software.
2. Connection cables must be ordered separately