Direct Access Parameter Information
https://www.toshiba.com/tic/
87
Optional V/I Terminal Voltage/Current Selection
Program
Frequency
V/I Settings
This parameter is used to set the AI2 input terminal to receive
either current or voltage as a control signal.
Note: The Expansion IO Card Option 2 option board (P/N
ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2
instruction manual (P/N
58686) for additional information on the function of this terminal.
Settings:
0 — Voltage Input
1 — Current Input
Direct Access Number —
F109
Parameter Type —
Selection List
Factory Default —
Voltage Input
Changeable During Run —
No
Always ON Terminal Function 1
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the virtual dis
-
crete input terminal ON. As a virtual terminal, the ON control ter
-
minal exists only in memory and is considered always to be in its
True (connected to CC) state.
It is often practical to assign a function to this terminal that the
user desires to be maintained regardless of external conditions or
operations.
This parameter sets the programmable ON terminal to one of the
user-selectable functions listed in
Direct Access Number —
F110
Parameter Type —
Selection List
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
No
Input Terminal 1 (F) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the F discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable
F
terminal to one of the
user-selectable functions listed in
Direct Access Number —
F111
Parameter Type —
Selection List
Factory Default—
Forward
Forward
Changeable During Run —
No
Input Terminal 2 (R) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the R discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable R terminal to one of the
user-selectable functions listed in
Direct Access Number —
F112
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......