74
https://www.toshiba.com/tic/
Direct Access Parameter Information
Command Mode
Program
Fundamental
Standard Mode Selection
The Command Mode Selection establishes the source of the
command input for the ASD. Command inputs include Run, Stop,
Forward, etc. The Override feature may supersede the Com
-
mand Mode Selection setting (see
).
Settings:
0 — Terminal Board
2 — EOI Keypad
3 — RS485/BACnet
4 — Communication Option Board
Direct Access Number —
F003
Parameter Type —
Selection List
Factory Default —
Terminal
Board
Changeable During Run —
No
Frequency Mode 1
Program
Fundamental
Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the fre
-
quency-control input for the ASD. The Frequency Mode 2 setting
or the Override feature may supersede the Frequency Mode 1
setting.
Note: Only Bolded items from the Settings list below may be
placed in the Override Mode. See the section titled
Command Mode and Frequency Mode Control on pg. 33
for
additional information on the Override feature.
Settings:
1 —
V/I
2 — RR
3 — RX
5 — EOI Keypad
6 —
RS485/BACnet
7 — Communication Option Board
8 — RX2 (AI1 Option)
9 —
Option V/I (AI2 Option)
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
Direct Access Number —
F004
Parameter Type —
Selection List
Factory Default —
RR
Changeable During Run —
No
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......