262
https://www.toshiba.com/tic/
Direct Access Parameter Information
Table 15. My Function Operator Selections.
My Function Computational Selections
Input
Function
Command
Function Name
Function Description
0
NOP (No Opera
-
tion)
Disables the My Function feature.
1
ST
Execute data read/transfer.
2
STN
Execute inverted data read/transfer.
3
AND
Logical product of A AND B.
4
ANDN
Logical product of A AND B.
5
OR
Logical sum of A OR B.
6
ORN
Logical sum of A OR B.
7
EQ
Compares data — Outputs 1 if Equal; 0 if not Equal.
8
NE
Compares data — Outputs 0 if Equal; 1 if not Equal.
9
GT
Compares data — Outputs 1 if A>B; 0 if A
B.
10
GE
Compares data — Outputs 1 if A
B; 0 if A
B.
11
LT
Compares data — Outputs 1 if A
B; 0 if A
B.
12
LE
Compares data — Outputs 1 if A
B; 0 if A>B.
13
ASUB
Outputs absolute difference between A and B — |A–B|
14
FB_ON_DELAY
(Timer)
Enables the On response time delay settings of My Function Time
Data 1 – 5 (
) for My Function Data.
15
FB_OFF_DELAY
(Timer)
Enables the Off response time delay settings of My Function Time
Data 1 – 5 (
) for My Function Data.
16
FB_COUNTER1
(Timer)
Outputs a 1 upon reaching the pulse count setting of
17
FB_COUNTER2
(Timer)
Outputs a 1 upon reaching the pulse count setting of
18
FB_PEEK_HOLD
Outputs the peak output value since powering up or since the last
reset.
19
SET
Sets data.
20
RESET
Resets data.
21
CLR
Clears data.
22
CLRN
Retains data.
Содержание DN-68249-003