Direct Access Parameter Information
https://www.toshiba.com/tic/
149
Process Increasing Rate
Program
Feedback
Feedback Settings
This parameter is used to limit the rate that the output of the ASD
may increase for a given difference in the speed reference and
the PID feedback value.
Direct Access Number —
F372
Parameter Type —
Numerical
Factory Default —
10.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Process Decreasing Rate
Program
Feedback
Feedback Settings
This parameter is used to limit the rate that the output of the ASD
may decrease for a given difference in the speed reference and
the PID feedback value.
Direct Access Number —
F373
Parameter Type —
Numerical
Factory Default —
10.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Frequency Command Detection Range
Program
Feedback
Feedback Settings
While operating in the PID mode, this parameter reads the feed
-
back frequency. Once the feedback frequency is within the set
-
ting of this parameter (
) relative to the commanded
frequency, a properly configured output terminal is activated.
Available output terminal settings for this parameter include: FC =
RR, FC = RX, and FC = VI (see
), where
FC is the frequency command and RR, RX, and VI are the input
terminals of the received feedback.
Direct Access Number —
F374
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Number of PG Input Pulses
Program
Feedback
PG Settings
This parameter is used to set the number of pulses output from a
shaft-mounted encoder that is used to indicate one revolution of
rotation (360°) of the motor or of the motor-driven equipment.
Direct Access Number —
F375
Parameter Type —
Numerical
Factory Default —
500
Changeable During Run —
No
Minimum — 1
Maximum — 9999
Number of PG Input Phases
Program
Feedback
PG Settings
This parameter determines the type of information that is sup
-
plied by the phase encoder.
Settings:
1 — Single Phase
2 — Two Phase
3 — Two Phase (Polarity Inversion)
Direct Access Number —
F376
Parameter Type —
Selection List
Factory Default —
Two Phase
Changeable During Run —
No
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......