Direct Access Parameter Information
https://www.toshiba.com/tic/
147
PID Feedback Integral (I) Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the Integral function
affects the output signal. The smaller the value here, the more
pronounced the effect of the integral function on the output sig
-
nal.
Direct Access Number —
F363
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.00
PID Deviation Upper Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feed
-
back may increase the output signal.
Direct Access Number —
F364
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — Lower-Limit Freq.
(
Maximum — Upper-Limit Freq.
(
Units — Hz
PID Deviation Lower Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feed
-
back may decrease the output signal.
Direct Access Number —
F365
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — Lower-Limit Freq.
(
Maximum —
Upper-Limit Freq.
Units — Hz
PID Feedback Differential (D) Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the Differential func
-
tion affects the output signal. The larger the value entered here,
the more pronounced the affect of the differential function for a
given feedback signal level.
Direct Access Number —
F366
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.55
Process Upper Limit
Program
Feedback
Feedback Settings
Selecting Process PID at parameter
allows for this parame
-
ter setting to function as the Upper Limit while operating in the
PID Control mode.
Direct Access Number —
F367
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — Lower-Limit Freq.
Maximum — Upper-Limit Freq.
Units — Hz
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......