Direct Access Parameter Information
https://www.toshiba.com/tic/
141
Carrier Frequency Control Mode
Program
Special
Carrier Frequency
This parameter provides for the automatic decrease of the car
-
rier frequency.
Select 1 to decrease the Carrier Frequency setting as a function
of an increased current requirement.
Selection 2 or 3 may also include an output voltage drop as a
function of an increased current requirement. The Carrier Fre
-
quency should be set below 4 kHz.
Settings:
0 — No Decrease and No Limit
1 — Valid Decrease and No Limit
2 — No Decrease and Limit Small Pulse
3 — Valid Decrease and Limit Small Pulse
4 — Dancer Control
5 — Option V/I (AI2 Option)
Direct Access Number —
F316
Parameter Type —
Selection List
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
No
Regenerative Over-Excitation Upper Limit
Program
Protection
Stall
This parameter is enabled by setting
to 2 or 3 and estab
-
lishes the maximum threshold energy level that may be fed back
from the motor during regeneration. If this setting is exceeded, an
Over-Voltage Trip will be incurred.
Note: This parameter setting may increase deceleration times.
Direct Access Number —
F319
Parameter Type —
Numerical
Factory Default —
140
Changeable During Run —
No
Minimum — 100
Maximum — 160
Units — %
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......