3. Mode Setting
3.2 Interrupt generation timing setting
The interrupt generation timing of each input point can be selected either rising, falling
or both edges.
•
Rising edge (OFF to ON)
ON
OFF
OFF
Interrupt
Input
•
Falling edge (ON to OFF)
ON
OFF
OFF
Interrupt
Input
•
Both edges (OFF to ON and ON to OFF)
ON
OFF
OFF
Interrupt
Input
This setting is made by the DIP switches provided on the front of the CD332.
Mode UP
DOWN
Rising edge
ON
OFF
Falling edge
OFF
ON
Both edges
ON
ON
CHANGE DETECT
IN0
1
2
3
4
5
6
7
IN0
1
2
3
4
5
6
7
UP
DOWN
ON
ON
NOTE
(1) This setting is available for each input
point
individually.
(2) The factory setting is all ON.
(Both
edges)
(3) Changes of the DIP switches are
effective while power on.