– 30 –
59-EN
60-EN
EN
FR
Check code
Check code name
Indication on 7-segment display on the outdoor unit
Auxiliary code
P02
01: Compressor 1
02: Compressor 2
Boost circuit trouble
P03
—
Discharge temperature TD1 trouble
P04
01: Compressor 1
02: Compressor 2
High-pressure SW system operation
P05
00:
Phase missing detection/Phase order trouble
01: Compressor 1
02: Compressor 2
Compressor Vdc trouble
P07
01: Compressor 1
02: Compressor 2
Heat sink overheat trouble
P10
Detected indoor unit address
Indoor overflow trouble
P13
—
Outdoor unit flow back trouble detected
P15
01: TS condition
02: TD condition
Gas leak detection
P17
—
Discharge temperature TD2 trouble
P19
Detected outdoor unit number
4-way valve inverse trouble
P20
—
High-pressure protective operation
P22
#0: Element short circuit
#E: Vdc voltage trouble
#1: Position detection circuit trouble
#2: Input current sensor trouble
#3: Motor lock trouble
#C: Sensor temperature trouble (No TH sensor)
#4: Motor current trouble
#D: Sensor short circuit/release trouble (No TH
sensor)
#5: Synchronization/step-out trouble
*Put in Fan IPDU No. in [#] mark.
Outdoor fan IPDU trouble
P26
01: Compressor 1
02: Compressor 2
IPM short protection trouble
P29
01: Compressor 1
02: Compressor 2
Compressor position detecting circuit trouble
*1 IPDU number information
01: Compressor 1 trouble
02: Compressor 2 trouble
03: Compressor 1 and 2 trouble
08: Fan 1 trouble
09: Compressor 1, Fan 1 trouble
0A: Compressor 2, Fan 1 trouble
0B: Compressor 1 and 2, Fan 1 trouble
11: Compressor 1, Fan 2 trouble
12: Compressor 2, Fan 2 trouble
13: Compressor 1 and 2, Fan 2 trouble
18: Fan 1 and 2 trouble
19: Compressor 1, Fan 1 and 2 trouble
1A: Compressor 2, Fan 1 and 2 trouble
1B: All
1122001101_EN FR.indd 30
1122001101_EN FR.indd 30
7/8/16 2:37 PM
7/8/16 2:37 PM