IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important
instructions for the BLACK GOLD TB
Series that should be followed during
the installation, operation, and maintenance of the UPS Systems.
The maximum ambient temperatures in which the UPS should be operated or stored is 40°C (104
°
F).
The nominal battery voltage for these models is 72VDC.
Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
When replacing batteries, use the same number and type of sealed, lead acid batteries (do not mix types
of batteries).
Model Capacity
BLACK GOLD
TB 2.0kVA
Manufacture
Yuasa
Type
NPH5-12FR
Quantity
6
CAUTION
Misuse of this equipment could result in human injury and equipment
damage. In no event will Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury that may result from the use of this equipment.
CAUTION
Do not dispose of the batteries in a fire. The batteries may explode.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is harmful to
the eyes and skin and could also be toxic.
WARNING
This unit contains sealed lead acid batteries. Lack of preventative
maintenance could result in batteries exploding and emitting gasses and/or
flame. An authorized, trained technician must perform annual preventative maintenance.
WARNING
Failure to replace a battery before it becomes exhausted may cause the
case to crack, possibly releasing electrolytes from inside the battery, and
resulting in secondary faults such as odor, smoke, and fire.