70
H7 ASD Operation Manual
OUT1 Output Terminal Assignment
Program
⇒
Terminal Selection Parameters
⇒
Output Terminal
Assignment
⇒
OUT1
This parameter sets the functionality of the OUT1 (A & C) output terminals to
1 of the 60 possible functions that are listed in
.
The on and off delay times of the OUT1 terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F130
Parameter Type — Selection List
Factory Default — Low
Changeable During Run — No
OUT2 Output Terminal Assignment
Program
⇒
Terminal Selection Parameters
⇒
Output Terminal
Assignment
⇒
OUT2
This parameter sets the functionality of the OUT2 (A & C) output terminals to
1 of the 60 possible functions that are listed in
.
The on and off delay times of the OUT2 terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F131
Parameter Type — Selection List
Factory Default — RCH (A/D Complete)
Changeable During Run — No
FL Output Terminal Assignment
Program
⇒
Terminal Selection Parameters
⇒
Output Terminal
Assignment
⇒
FL
This parameter sets the functionality of the FL output terminals to 1 of the 60
possible functions that are listed in
.
The on and off delay times of the FL terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F132
Parameter Type — Selection List
Factory Default — Fault
Changeable During Run — No
Output #4 Terminal Assignment
Program
⇒
Terminal Selection Parameters
⇒
Output Terminal
Assignment
⇒
4
This parameter sets the functionality of the output #4 terminals to 1 of the 60
possible functions that are listed in
.
The on and off delay times of the #4 terminals may be adjusted to provide more
response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F133
Parameter Type — Selection List
Factory Default — LL
Changeable During Run — No
The FLA and FLC contacts are rated at
2A/250 VAC. The FLB contact is rated
at 1A/250 VAC.
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...