H7 ASD Operation Manual
57
Preset Speed #6
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
6
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed #6. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
for further
information on this parameter).
Direct Access Number — F023
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
)
Maximum — Upper Limit (
)
Units — Hz
Preset Speed #7
Program
⇒
Pattern Run Control
⇒
Preset Speeds
⇒
7
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed #7. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
for further
information on this parameter).
Direct Access Number — F024
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (
)
Maximum — Upper Limit (
)
Units — Hz
Low Speed Signal Output Frequency
Program
⇒
Terminal Selection Parameters
⇒
Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD output
is at or below this setting (see
for the available output
assignments).
Direct Access Number — F100
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (
)
Units — Hz
Speed Reach Frequency
Program
⇒
Terminal Selection Parameters
⇒
Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter
, will provide a signal at an
output terminal that can close an appropriately configured output contact (see
for the available output assignments).
Direct Access Number — F101
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (
)
Units — Hz
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...