48
H7 ASD Operation Manual
Direct Access Parameter Information
The H7 ASD has the ability to allow the user direct access to the motor control functions. The functions
listed below have an associated Parameter Number which accesses its setting. There are two ways in
which the motor-control parameters may be accessed for modification: Program
⇒
applicable menu item
or Program
⇒ Direct Access ⇒ applicable parameter number.
Both methods access the parameter via
the Program mode. Once accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop
an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note: The setup procedures included within this section may require a
Reset
before performing the procedure.
Application-specific settings may then be performed. The pre-Reset conditions may be saved (see F007).
The LED Keypad is under development and is unavailable at the time of this release.
Direct Access Parameters/Numbers
Automatic Accel/Decel #1
Program
⇒
Fundamental Parameters
⇒
Accel/Decel #1 Settings
When enabled, the ASD adjusts the acceleration and deceleration rates
according to the applied load. The adjusted acceleration and deceleration times
range from 12.5% to 800% of the programmed values for Acceleration Time
#1 (
).
Note: The motor and the load must be connected prior to selecting Automatic
Accel/Decel.
Direct Access Number — F000
Parameter Type — Check Box
Factory Default — Not Selected
Changeable During Run — No
Command Mode Selection
Program
⇒
Fundamental Parameters
⇒
Standard Mode Set
The Command Mode Selection establishes the source of the command inputs
for the ASD. Command inputs include Run, Stop, Forward, etc.
The Control Terminal Strip selection enables the Local|Remote key to switch
the controlling input of the ASD between the Control Terminal Strip and the
EOI.
The EOI selection places the system in the Local mode and receives commands
from the EOI only.
The RS232/485 selection enables the Local|Remote key to switch the
controlling input of the ASD between the RS232/485 line and the EOI.
Settings:
Use Control Terminal Strip
Use LED Keypad Option
Use Common Serial (TTL)
Use RS232/485
Use Communication Card
Direct Access Number — F003
Parameter Type — Selection List
Factory Default — Use Control
Terminal Strip
Changeable During Run — No
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...