H7 ASD Operation Manual
143
Pattern Run
Program
⇒
Pattern Run Control Parameters
⇒
Pattern Run
This parameter Enables/Disables the Pattern Run mode. When enabled, this
feature allows up to 15 Preset Speeds to be run sequentially for a user-
determined amount of times.
Pattern Run Description
User-defined Preset Speeds are labeled 1 – 15 (see
F018
). The ID number of
any one of the fifteen frequencies (1 – 15) may be entered into the Speed # field
of the Pattern Run screen and run for the number of times entered into the
Repeat field (see
). The execution of grouped Preset Speeds in this
manner is called a Pattern Run.
Skip may be selected to ignore a Speed # field.
Pattern Run Setup
1.
Configure an unused discrete input terminal for Pattern #1 (2, 3, or 4). This
terminal will initiate the selected Pattern Run. The input terminal settings
may be configured via Program
⇒ Terminal
Selection Parameters
⇒
Input
Terminals
for available input terminal settings).
2.
Enable the Pattern Run mode of operation via Program
⇒ Pattern Run
Control Parameters
⇒
Pattern Run
⇒ Enable/Disable (check box).
3.
Configure the Preset Speeds that are to be used as the Group Speed set of
frequencies via Program
⇒ Pattern Run Control Parameters ⇒
Preset
).
4.
Configure the Group Speeds by associating the Preset Speeds that are to
be enabled and grouped (from step 3) as Group Speed 1 (2, 3, or 4) via
Program
⇒ Pattern Run Control Parameters ⇒
Speeds. Set the Repeat
field to the number of times that the selected group is to be run. Set unused
speed settings to Skip.
5.
From the Remote mode (Local|Remote light is off), initiate a Run
command (e.g., F and/or R terminal On).
6.
Connect the input terminal that was configured in step 1 to CC and the
Pattern Run will start and continue as programmed. Open the connection
to stop the Pattern Run before its conclusion.
for further information on this parameter.
Direct Access Number — F520
Parameter Type — Check Box
Factory Default — Disable
Changeable During Run — No
Pattern Run Mode Restart Command
Program
⇒
Pattern Run Control Parameters
⇒
Pattern Run
This parameter sets the start condition of subsequent Pattern Runs after the
initial Pattern Run has been terminated or has completed its programming.
Settings:
Reset
Continue
Direct Access Number — F521
Parameter Type — Selection List
Factory Default — Disable
Changeable During Run — No
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...