98
H7 ASD Operation Manual
BIN Speed Reference Setpoint #1 (frequency)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
See
for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of
.
Direct Access Number — F229
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
BIN Speed Reference Setpoint #2 (%)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control or the Torque Control mode.
See
for further information on this setting.
This parameter sets BIN Reference Setpoint #2 (direction/torque/frequency)
and is entered as 0 to 100% of the BIN binary input word 11111111 (255
D
).
Direct Access Number — F230
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
BIN Speed Reference Setpoint #2 (frequency)
Program
⇒
Frequency Setting Parameters
⇒
Speed Reference
Setpoints
⇒
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
See
for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of
.
Direct Access Number — F231
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
BIN Torque Reference Setpoint #1 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
See
for further information on this setting.
This parameter sets BIN Torque Reference Setpoint #1 (%) and is entered as
-250 to +250% of the rated torque.
Direct Access Number — F232
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...