Operating conditions
•
The units referred to within this manual conform with the protection requirements of Directives 89/336/EEC
Electromagnetic Compatibility and 73/23/EEC Low voltage.
•
Operating conditions of the unit are as follows:
Outdoor temperature
-5 ~ 43°C
Cooling
-15 ~ 21°C
Heating
Room temperature
18 ~ 32°C
Cooling
15 ~ 29°C
Heating
Room humidity
<80%
Cooling
Note 1: Cooling capacity is rated at the following temperature conditions:
Indoor air inlet temperature
27°C DB, 19°C WB.
Outdoor air inlet temperature
35°C DB.
Note 2: Heating capacity is rated at the following temperature conditions:
Indoor air inlet temperature
20°C DB.
Outdoor air inlet temperature
7°C DB, 6°C WB.
Note 3: For details about the Outdoor unit, Indoor units or Remote Controller installation refer to the relevant literature, i.e.
Installation Instructions supplied with the units.
Note 4: Operatives handling refrigerants must be suitably qualified in accordance with local and national codes of practice
and statutory requirements.
Note 5: Legislation may regulate the removal of waste refrigerant from the systems. We advise awareness of any
regulations and duty of care. Waste refrigerant must NEVER be discharged to atmosphere.
Note 6: Electrical work should be in accordance with all relevant codes of practice and should be carried out by suitably
qualified personnel.
Note 7: Metric/Imperial pipe conversion.
Diameter (mm)
6.4
9.5
12.7
15.9
19.0
2.0
28.6
34.9
41.3
54.1
Nominal diameter (inch)
1/4
3/8
1/2
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
2-1/8
Note 8: Within this manual:
ODU
= Outdoor Unit
IDU
= Indoor Unit
R/C
= Remote Controller
D.O.L.
= Direct On-Line compressor
INV
= Inverter ODU
FIX
= Fixed-speed ODU
DB
= Dry Bulb
WB
= Wet Bulb
Mg-Sw = Magnetic Contactor
IOL
= Inner Overload Relay
OCR
= Over Current Relay
IGBT
= Inverter Gate Bi-Polar Transistor
Note 9: MPaG
⇒
kgf/cm
2
G conversion multiplier
1.0 MPaG = 10.2 kgf/cm
2
G
2