13.5 Audible Alarm Functions
An audible alarm (buzzer) will sound when the UPS is in the battery
backup mode, has a fault, has low battery voltage, or is
in an overload condition. The buzzer will also beep each time an effective item is touched on the touchscreen. The following
chart shows the buzzer pattern durations for each condition. Time units are shown in seconds.
FIGURE 13.3: AUDIBLE ALARMS
Condition
Audible Pattern
Any Fault (Intermittent buzz until fault clears)
0.5 s
0.5 s
Switch to Backup (Single five-second buzz)
5.0 s
Backup Operation (Intermittent buzz once every
ten seconds)
9.0 s
1.0 s
UPS Battery Shutdown Voltage
(Batt. Voltage 79% Normal)
5.0 s
Warnings:
OL110 (Overload Timer)
LB (Low
Battery – Batt. Voltage 90% Normal)
BLFN (
Battery Life Pre-alarm – Batt expires in 6
mo.)
BLFE (
Battery Life End)
CHRGOV (Charger Over Voltage)
BTSTFL (
Battery Test Fail)
BOH (
Battery Overheat)
AOH (Ambient Overheat)
CLMT (Current Limit)
DCER (Display Disconnected)
BDEPL (
Battery Depletion)
1.0 s
1.0 s
Touching Effective Item on
Touchscreen
0.1 s
The buzzer can be silenced most easily by pressing the Buzzer Silent button on the Quick Access Toolbar.
Alternatively, the buzzer can also be silenced by selecting the Settings tab, then set the Buzzer Silent parameter to Disable.
This will turn off the buzzer for the current alarm status, but the buzzer will still sound when the next Fault/Warning condition
occurs.
The buzzer can be disabled permanently by selecting the Settings tab then setting the parameter
Buzzer Disable
to
Disable. This will disable the alarm so that no alarm sounds for any Fault or Warning condition.
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......