42
4200FA Installation and Operation Manual
5.10
4200FA Efficiencies and Thermal Losses at Various Loads
5.10.1 Eff. Vs. Load Table – 4200FA , No Internal Transformers *
15 kVA int Batt
25 kVA int Batt
30 kVA int Batt
50 kVA int Batt
100% Load *
87.5%
89.2%
87.5%
88.3%
*Contact the factory for additional information on efficiency vs. load curves.
5.10.2 Thermal Loss in BTU/Hr. - 4200FA , No Internal Transformers *
15 kVA int Batt
25 kVA int Batt
30 kVA int Batt
50 kVA int Batt
100% Load
6,685
9,263
13,370
20,481
75% Load
5,571
7,237
10,396
16,259
50% Load
4,724
5,565
8,388
13,853
25% Load
3,776
4,342
7,028
9,182
0% Load
1,798
2,409
2,890
3,722
5.10.3 Eff. Vs. Load Table – 4200FA with Input Transformer *
15 kVA w/ 1 Xfmr
25 kVA w/1 Xfmr
3 kVA w/1 Xfmr
50 kVA w/ 1Xfmr
100% Load *
86.5%
88.2%
86.5%
86.5%
*Contact the factory for additional information on efficiency vs. load curves.
5.10.4 Thermal Loss in BTU/Hr. – 4200FA with Input Transformer *
15 kVA w/ 1 Xfmr
25 kVA w/1 Xfmr
30 kVA w/1 Xfmr
50 kVA w/ 1Xfmr
100% Load
7,388
10,351
14,775
24,625
75% Load
6,069
8,063
11,463
19,425
50% Load
5,090
6,141
9,083
16,044
25% Load
3,987
4,656
7,433
10,360
0% Load
2,730
4,077
4,892
6,403
5.10.5 Eff. Vs. Load Table – 4200FA with Input and Output Transformers *
15 kVA w/ 2 Xfmr
25 kVA w/2 Xfmr
30 kVA w/2 Xfmr
50 kVA w/ 2 Xfmr
100% Load *
85.1%
86.7%
85.1%
85.8%
*Contact the factory for additional information on efficiency vs. load curves.
5.10.6 Thermal Loss in BTU/Hr. – 4200FA with Input and Output Transformers *
15 kVA w/ 2 Xfmr
25 kVA w/2 Xfmr
30 kVA w/2 Xfmr
50 kVA w/ 2 Xfmr
100% Load
8,424
12,074
16,848
26,327
75% Load
6,925
9,371
13,037
20,560
50% Load
5,680
7,000
10,277
16,988
25% Load
4,337
5,168
8,105
10,827
0% Load
2,730
4,077
4,892
6,403
* The efficiencies and thermal loss are listed no-load, 25/50/75/100% loads for three sets of conditions:
•
UPS without input/output internal transformers
•
UPS with Internal input isolation transformer
•
UPS with internal input isolation transformer and autotransformer
(NOTE: The efficiencies and thermal values listed are representative only. Individual performance may be different due to variations
in manufacture, transformer type, and transformer performance at different loads.)
Содержание 4200FA CT
Страница 2: ...4200FA Installation and Operation Manual ...
Страница 4: ...4200FA Installation and Operation Manual ...
Страница 10: ...iv 4200FA Installation and Operation Manual This Page Intentionally Left Blank ...
Страница 14: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Страница 85: ...4200FA Installation and Operation Manual 75 APPENDIX A Seismic Anchorages ...
Страница 86: ...76 4200FA Installation and Operation Manual ...
Страница 87: ...4200FA Installation and Operation Manual 77 ...
Страница 88: ...78 4200FA Installation and Operation Manual ...
Страница 96: ......
Страница 97: ......