82
model 3000 Ethernet Module / DS Connection Module Operation Manual
Appendix A Specifications
A
Table A-2 General Specifications (EN751, EN751A, EN761, FN711)
Item
Specifications
EN751A
EN751
EN761
FN711
Working temperature range
(Product ambient temperature)
Vertical installation: 0 to 55
o
C
Working humidity range
10 to 95% RH (without condensation)
Storage temperature range
-25 to 70
o
C
Storage humidity range
5 to 95% RH (without condensation)
Source voltage range
4.75 to 5.25 VDC (Rated voltage :5.0VDC)
Current drain
(at rated power input)
1.1 A or less
(5.0VDC)
1.8A or less
(5.0VDC)
Power consumption
(at rated power input)
5.5W or less
9W or less
Insulation resistance (between
signal and F.G.)
10 megohms or more
Withstand boltage
(between signal and F.G.)
500 VAC for 1 minute
Dust
0.3 mg/m
3
or less
Vibration resistance
4.9m/s
2
1.5mm
p-p
Shock resistance
19.6m/s
2
(3 times with power off)
Grounding
Class D (Grounding resistance: 100 ohms or less)
Cooling
Natural air
cooling
Forced air cooling
Module dimensions
249 (H)
×
35 (W)
×
112.7 (D) mm
Weight
500g or less
700g or less
Communication interface
100BASE-TX/10BASE-T (automatically selected)
Single bus
Dual bus
Backup
Caution
The EN751, EN761, and FN711 modules receive power supply from the main power unit (PS*)
for memory backup. If these modules are removed from the base unit, therefore, their memory
data will be deleted. Save the necessary data using the Engineering Tool before removing them
from the base unit.
Содержание 3000 series
Страница 13: ...CONTENTS 6F8C0878 xi E Sample Programs 91 F Return Code List 103 G Option switch List 107 ...
Страница 14: ......
Страница 26: ......
Страница 72: ......
Страница 76: ......
Страница 82: ......
Страница 100: ......
Страница 102: ......
Страница 104: ......
Страница 116: ......
Страница 120: ......
Страница 122: ......
Страница 126: ......