TO BEGIN: SET
BATTERY TEST
###%
Or
Executes battery test
and returns to Data
Setting Screens
Cont'd from Bat. test interval Data Setting Screen page 30
CLEAR TIMER SET
TO CHANGE:SELECT
CLEAR TIMER SET
TO ACCEPT:SET
Only possible
condition
Cancels timer setting
and returns to Data
Setting Screens
Cont'd from Clear Timer Data Setting Screen page 30
DEFAULT SETTINGS
TO CHANGE:SELECT
DEFAULT SETTINGS
TO ACCEPT:SET
Only possible
condition
Initializes default
setting and returns to
Data Setting Screens
Cont'd from Default Data Data Setting Screen page 30
35
TOSHIBA
Display Screens (cont'd)
Data Setting Screen
The following screens show the setting procedure for setting the data variables. They are accessed
from the main 'data setting screens' (see page 30) when the key is pressed:
General Safety
Inspections & Precautions
Connections
Equipment
Equipment
Specifications
Equipment
Display Screens
Manual Run/Stop
Protection System
Maintenance & Options
Dimensions &
Weights
Index
Reference
Operations
Key Functions
Display &
This parameter has no options to set. A
battery test will be performed once the
SHIFT + SET button is pressed.
If the BAT TEST INHIBIT message is
displayed, it indicated that a battery test has
been performed recently. The UPS will not
allow frequent battery tests to insure that the
batteries remain in a fully charged state.
VOLTAGE ADJ: +0
TO CHANGE:SELECT
VOLTAGE ADJ: +5
TO ACCEPT:SET
VOLTAGE ADJ: +0
TO ACCEPT:SET
VOLTAGE ADJ: -5
TO ACCEPT:SET
Returns to
Data Setting Screens
(with new value
applied)
Loops through three
possibilities
Cont'd from Voltage Adj. Data Setting Screen page 30
This parameter allows the user to offset
the output voltage (while the unit is running
on-line), by 1% increments between -5% to
+5%.
Default value is +0
This parameter has no options to set.
Pressing the select button while this message
is displayed will reset all parameters to their
default values.
+
+
+
+
Shift
Select
Shift
Select
Shift
Select
Shift
Select
Set
Monitor
Set
Monitor
Set
Monitor
Set
Monitor
+
+
Shift
Select
Shift
Select
Set
Monitor
Set
Monitor
Shift
Select
BATTERY TEST INHIBIT
This parameter has no options to set.
Pressing the SHIFT + SET button while this
message is displayed will cancel timer setting.
VOLTAGE ADJ: +5
TO CHANGE:SELECT
VOLTAGE ADJ: -5
TO CHANGE:SELECT