TOSHIBA
Model
Amp rating
Fuse model no.
600 VA
15.0A
LittleFuse 314015
800 VA
15.0A
LittleFuse 314015
1000 VA
15.0A
LittleFuse 314015
1200 VA
15.0A
LittleFuse 314015
1500 VA
15.0A
LittleFuse 314015
2000 VA
15.0A
LittleFuse 314015
500 VA Plus
6.25A
Bussman MDL-6.25
750 VA Plus
8.0A
Bussman MDL-8
1000 VA Plus
10.0A
Bussman MDA-10
1500 VA Plus
15.0A
Bussman MDA-10
7.0
Preventive Maintenance/Parts Replacement
7.1
Preventive Maintenance
Toshiba's 1400 Series of uninterruptible power systems have been designed to provide
years of trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the
unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
If the atmosphere of the installation site is very dusty, use a vacuum cleaner to
periodically remove dust accumulations from the system.
7.2
Parts Replacement
The following list shows recommended intervals for periodic replacement of certain
UPS parts.
1)
Batteries: In order to maintain system reliability, the UPS unit's batteries
should be replaced once every 3 to 5 years. To ensure reliable operation, all
of the batteries should be replaced at the same time.
2)
Aluminum electrolytic capacitors: Replace once every 5 years.
3)
Fuses: Replace once every 7 years (see output fuse rating chart below).
4)
Cooling fan: Replace once every 3 years.
7.3
Input/Output Fuse Rating Chart
The following chart shows the recommended fuses for all UPS sizes.
7 - 1
Fuse rating