Troubleshooting

Problem

Cause

Solution

The unit doesn’t work and the power-

• 

on  light  is  off,  even  after  connecting 

the  supply  voltage    and  selecting  

“AUTO” mode.

Wrong input connection.

• 

Phase failure.

• 

Over-voltage supply.

• 

Connect accurately.

• 

Check the three phases.

• 

Verify and measure the supply voltage.

• 

Pump OVERLOAD alarm trips.

• 

Excessive motor consumption. 

• 

Low overcurrent adjustment.

• 

Input phase failure.

• 

Verify the pump. The pump motor is overloaded. 

• 

Check the motor consumption and adjust the current.

• 

Check the three supply phases.

• 

Pump UNDERLOAD alarm trips.

• 

Low current consumption <1,5 A.

• 

 

Input phase failure.

• 

Motor not connected.

• 

Check the pump (no water in suction, stuck pipe, 

• 

etc...).

Check the three supply phases.

• 

Connect the motor.

• 

The pump doesn’t re-start.

• 

Re-start time is set to “0”.

• 

Adjust the re-start time.

• 

The pump starts & stops on the mini-

• 

mum level probe (2 probes mode).

Maximum and minimum level probes inverted.

• 

Place the probes in the correct position.

• 

Level control doesn’t work correctly.

• 

Incorrect ground connection.

• 

Damaged wires.

• 

Check the ground connection.

• 

Check the integrity of the wires.

• 

The pump doesn’t start, low level light 

• 

is  off,  External  ON/OFF  is  not  being 

used.

External ON/OFF is open circuit.

• 

Place a jumper over the External ON/OFF terminal 

• 

blocks.

The pump doesn’t start, low level light 

• 

is  off,  External  ON/OFF  is  not  being 

used.

External ON/OFF is open or no supply voltage 

• 

is applied.

Check the external remote control.

• 

The circuit breaker trips on start-up.

• 

Excessive current consumption.

• 

Verify the pump and its wiring.

• 

The pump doesn’t stop with External 

• 

ON/OFF or level control.

“MANUAL” mode selected.

• 

Select the “AUTO” mode.

• 

Specifications

Supply voltage

Single voltage 230 or 400 V~ (according to the model) -20% +30%

Power

10 CV (7,5 kW) at 400 V~

Overload/Underload   adjustment  1,5 - 18 A (alarm trip in 7 sec.) Re-start time: 0-2 Hours

Probes: Supply voltage/Sensitivity

24 V~ / 9 Kohm. (protected against storms transient). Wire distance: 

200 m. max.  Min. section 0,5 mm.

Remote for EXTERNAL ON/OFF connection Contact or voltage 6 to 250 V~/V=

Terminal blocks wiring size

10 mm² (power) 4 mm² (control)

Protection

Overload, Underload, Phase failure, Pump wiring f Wrong 

control wiring

Size/Weight/Protect./Temp.

230 (high) x 180 (width) x 125 (deep) /1820 g / IP56 / -10 + 55ºC

Autovía A-92, Km. 6,5 - 41500 - Alcalá de Guadaíra - SEVILLA - ESPAÑA

Tfno. 34 954 999 900 - Fax. 34 95 425 93 60 / 70

www.toscano.es - [email protected]

TOSCANO LINEA ELECTRONICA, S.L.

Service line

(+34) 954 999 900

ISO9001:2000 Certificated by Bureau Veritas

EC DECLARATION OF COMPLIANCE WITH THE “LOW VOLTAGE” & “ELECTROMAGNETIC COMPATIBILITY” DIRECTIVES.

TOSCANO LINEA ELECTRONICA, S.L. declares that the equipment described in this manual complies with the provisions of the modified “LOW VOLTAGE” directive (Directive DC 2004/108/CE) and with the 

modified “ELECTROMAGNETIC COMPATIBILITY” directive (Directive DC 2006/95/CE) and with national legislation based upon them. It also complies with the provisions of the following European standards 

and draft standards: 

NF EN 60.439-1 / EN 50.081-1 / EN 50.082-2.