Troubleshooting
Problem
Cause
Solution
The unit doesn’t work and the power-
•
on light is off, even after connecting
the supply voltage and selecting
“AUTO” mode.
Wrong input connection.
•
Phase failure.
•
Over-voltage supply.
•
Connect accurately.
•
Check the three phases.
•
Verify and measure the supply voltage.
•
Pump OVERLOAD alarm trips.
•
Excessive motor consumption.
•
Low overcurrent adjustment.
•
Input phase failure.
•
Verify the pump. The pump motor is overloaded.
•
Check the motor consumption and adjust the current.
•
Check the three supply phases.
•
Pump UNDERLOAD alarm trips.
•
Low current consumption <1,5 A.
•
Input phase failure.
•
Motor not connected.
•
Check the pump (no water in suction, stuck pipe,
•
etc...).
Check the three supply phases.
•
Connect the motor.
•
The pump doesn’t re-start.
•
Re-start time is set to “0”.
•
Adjust the re-start time.
•
The pump starts & stops on the mini-
•
mum level probe (2 probes mode).
Maximum and minimum level probes inverted.
•
Place the probes in the correct position.
•
Level control doesn’t work correctly.
•
Incorrect ground connection.
•
Damaged wires.
•
Check the ground connection.
•
Check the integrity of the wires.
•
The pump doesn’t start, low level light
•
is off, External ON/OFF is not being
used.
External ON/OFF is open circuit.
•
Place a jumper over the External ON/OFF terminal
•
blocks.
The pump doesn’t start, low level light
•
is off, External ON/OFF is not being
used.
External ON/OFF is open or no supply voltage
•
is applied.
Check the external remote control.
•
The circuit breaker trips on start-up.
•
Excessive current consumption.
•
Verify the pump and its wiring.
•
The pump doesn’t stop with External
•
ON/OFF or level control.
“MANUAL” mode selected.
•
Select the “AUTO” mode.
•
Specifications
Supply voltage
Single voltage 230 or 400 V~ (according to the model) -20% +30%
Power
10 CV (7,5 kW) at 400 V~
Overload/Underload adjustment 1,5 - 18 A (alarm trip in 7 sec.) Re-start time: 0-2 Hours
Probes: Supply voltage/Sensitivity
24 V~ / 9 Kohm. (protected against storms transient). Wire distance:
200 m. max. Min. section 0,5 mm.
Remote for EXTERNAL ON/OFF connection Contact or voltage 6 to 250 V~/V=
Terminal blocks wiring size
10 mm² (power) 4 mm² (control)
Protection
Overload, Underload, Phase failure, Pump wiring f Wrong
control wiring
Size/Weight/Protect./Temp.
230 (high) x 180 (width) x 125 (deep) /1820 g / IP56 / -10 + 55ºC
Autovía A-92, Km. 6,5 - 41500 - Alcalá de Guadaíra - SEVILLA - ESPAÑA
Tfno. 34 954 999 900 - Fax. 34 95 425 93 60 / 70
www.toscano.es - [email protected]
TOSCANO LINEA ELECTRONICA, S.L.
Service line
(+34) 954 999 900
ISO9001:2000 Certificated by Bureau Veritas
EC DECLARATION OF COMPLIANCE WITH THE “LOW VOLTAGE” & “ELECTROMAGNETIC COMPATIBILITY” DIRECTIVES.
TOSCANO LINEA ELECTRONICA, S.L. declares that the equipment described in this manual complies with the provisions of the modified “LOW VOLTAGE” directive (Directive DC 2004/108/CE) and with the
modified “ELECTROMAGNETIC COMPATIBILITY” directive (Directive DC 2006/95/CE) and with national legislation based upon them. It also complies with the provisions of the following European standards
and draft standards:
NF EN 60.439-1 / EN 50.081-1 / EN 50.082-2.