16 - EN
TAR1 400V / 230V
5
Programming
In order to program the
Ladebrückensteuerung
, open the housing
cover.
The programming works in a menu-controlled fashion. Carry out
all settings as specified in the
Programming procedure
chapter,
see also
Representation of the menu structure
. The
Program
overview
chapter shows the full scope of the menu.
Programming procedure
Proceed as follows to carry out programming settings:
1.
Press the
button to reach the programming of the con-
trol. The selection of the individual main menu (in the fol-
lowing referred to as "menu") appears on the LED display.
Up to 9 menus are provided.
2.
Navigate with buttons
to select the desired menu.
The LED display shows the current selection as value 1-9.
3.
Confirm the selection with the button
. The LED display
in the first digit now shows the menu which you are in. The
second digit shows the current menu item in this menu.
4.
Navigate with buttons
to select the desired menu
item. A total of up to 10 menu items is provided to you
(0-9). The LED display shows the current selection in the
second digit as value 0-9.
5.
Confirm the selection with the button
. The currently set
value for the respective menu item blinks on the LED dis-
play.
6.
Set the desired value using the buttons
. Depending
on the menu item, values between 0 and 99 can be
entered.
7.
Confirm the entry with the button
. The LED display
confirms the entry by 5-time blinking of the LED point and
by returning to the selection of the menu item.
8.
If you want to complete the programming, press the but-
ton
repeatedly until
– –
appears on the display.
9.
Confirm the selection with the button
to exit the pro-
gramming.
Representation of the menu structure
Menu
Menu item
Selection
1.
Activation of programming
2.
Menu selection
3.
Confirmation of the
main menu selection
4.
Selection of the menu
item
5. Confirmation of the
menu item selection
6. Setting of the desired value
7. Confirmation of the
setting
8. Navigation to the next
menu item or to exit
the programming
menu
9. Exit programming
Exit
Menu 1 Basic settings loading bridges
Overcurrent hydraulic motor (menu item 10)
Depending on the set current value, the control switches off the
pump if this value is exceeded.
In order to set the correct current value for the overcurrent, you
have to determine the actual value first. For adjusting, proceed as
follows: