Troubleshooting Guide
Problem
Cause
Remedy
Unit does not run
Power interruption
Check external power supply. Reset LCDI cord
control. Check circuit breakers and fuses. Re-
place or reset if necessary.
Condensate tank-full (tF indicated)
Empty tank
Thermostat set incorrectly
Check Mode setting and temperature setpoint
vs. room temperature. Reset if necessary.
Thermostat inoperable
Check for display on thermostat. Press power
switch and mode switches to determine if
thermostat responds. Replace thermostat if
necessary.
Thermostat displays error code
rE
room sensor failure
FE
freeze sensor failure
CF
compressor failure
Fr
coil freezing
tF
condensate tank full
Repair or replace room sensor.
Repair or replace freeze sensor.
Check for compressor problems.
Space too cold or refrigerant level low.
Condensate tank must be emptied
Electrical Panel Problem
- 24 volt transformer defective
- Fuse blown/overload tripped (TZ-60B)
- Loose wire
- Contactor coil defective
- Contactor stuck open, burned or dirty
- Replace transformer.
- Check and replace or reset if necessary.
- Check and tighten if necessary.
- Replace contactor.
- Repair or replace contactor.
Evaporator fan runs but
compressor and con-
denser fan do not.
Thermostat satisfied
The evaporator runs anytime the thermostat is
on. The compressor and condenser only run if
there is a demand for cooling.
Thermostat is in the compressor start delay
mode
Make sure there is a call for cooling then wait at
least five minutes for compressor to start.
Thermostat set for the wrong MODE
Set MODE to COOL.
Condensate jumper plug or condensate
pump not installed
Install jumper if a condensate tank is being
used. Attach pump if pump is used.
High pressure switch tripped or defective
Press reset button on high pressure switch.
Replace switch if necessary.
Loose or defective wires
Check for loose or shorted conductors. Secure
contact between wires and connectors. Repair
or replace as required.
Shorted or open run capacitor
Replace capacitor.
Defective compressor
Check for shorts, opens and grounds. Com-
pressor replacement should be done by a
service technician.
Содержание TZ-12B
Страница 15: ...Portable Air Conditioners 15 Wiring Schematic TZ 12B ...
Страница 16: ...TOPAZ Owner s Manual Wiring Schematic TZ 18B ...
Страница 17: ...Portable Air Conditioners 17 Wiring Schematic TZ 24B ...
Страница 18: ...TOPAZ Owner s Manual Wiring Schematic TZ 36B ...
Страница 19: ...Portable Air Conditioners 19 Wiring Schematic TZ 60B ...
Страница 20: ...TOPAZ Owner s Manual Wiring Schematic TZ 60B3 ...
Страница 21: ...Portable Air Conditioners 21 Wiring Schematic TZ 60B4 ...